Compute the line voltage and Yimpedance bases at each bus Co
Compute the line voltage and Y-impedance bases at each bus. Complete the table provided. T1: 3 - Single-Phase, 100 MVA, 34 kV/66.4 kV, X_e = 8% TL23 : z bar = j0.50ohm/mi, 75 miles L3: Z_delta = 150+j10ohm, 113.0 kV System Bases: 500 MVA, 115 kV at bus 2
Solution
TRANSFORMER T1:
XC=0.08 PU
XC PU=(XC ACTUAL/XC BASE)
XC ACTUAL=XC BASE*XC PU
XC BASE AT BUS 2=(115)^2/500=26.45 OHMS
XC BASE AT BUS 1=[(34/66.4)*115]^2/(500)=6.93 OHMS
XC ACTUAL AT BUS 3=75*j0.5=37.5 kohms
xc actual at bus 1= 6.93*j0.08=0.5544 kohms
xc actual at bus 2=26.45*j0.08=2.116 kohms
| BUS | VL,KV | Z,KOHMS |
| 1 | 34 | 0.5544 |
| 2 | 66.4 | 2.116 |
| 3 | 113.0 | 37.5 |