A residence has 1450 square feet of living space and is serv
A residence has 1450 square feet of living space, and is served at 240/120 V. The following information is known: 24 general use receptacles 2 laundry circuits 6 dedicated small appliance circuits Calculate the estimated demand after applying the appropriate demand factors.
Solution
Hello ,
I have gone through your problem and giving you aproximate solution for your load demand:
Load for 24 geneal receptacles : 24 X 90 VA=2160 VA
This will not be continues load so : 2160 X 0.75 = 1620
Load for 2 laundry 7000 VA IF WE CONSIDER cONTINOUSE LOAD THAN IT WILL BE APROX 1500 VA.
:2 X 1500VA ( considering Continues ) = 3000 VA
Load for6 dedicated load :6 X 1500VA= 9000 VA FOR cONTINUES
IT WILL BE 9000 x 1.25 = 11250
Total Other Loads:840 + 1200 + 1320+ 720 + 7500 + 850 + 4700 + 4560 = 21690VA
Total load : 37560 VA
IN KW : 37110 X 0.8 = 30048 == aprox 30000 W = 30 KW
30 KW