3 The 6bus power system in literature known as Ward and Hall
Solution
% Program to form Admittance Bus Formation without Transformer Tap setting
num = 6; % IEEE-6 bus systems..
 linedata = linedata(num); % Calling \"linedata.m\" for Line Data...
 fb = linedata(:,1);
 tb = linedata(:,2);
 r = linedata(:,3);
 x = linedata(:,4);
 b = linedata(:,5);
 a = linedata(:,6);
 z = r + 1i*x;
 y = 1./z;
 b = 1i*b;
nbus = max(max(fb),max(tb));
 nbranch = length(fb);
 Y = zeros(nbus,nbus);
 
 % Formation of the Off Diagonal Elements %
 for k=1:nbranch
 Y(fb(k),tb(k)) = Y(fb(k),tb(k))-y(k)/a(k);
 Y(tb(k),fb(k)) = Y(fb(k),tb(k));
 end
 
 % Formation of Diagonal Elements %
 for m =1:nbus
 for n =1:nbranch
 if fb(n) == m
 Y(m,m) = Y(m,m) + y(n)/(a(n)^2) + b(n);
 elseif tb(n) == m
 Y(m,m) = Y(m,m) + y(n) + b(n);
 end
 end
 end
 Y; % Bus Admittance Matrix%
Line data
% | From | To | R | X | B/2 | X\'mer | %
 % | Bus | Bus | pu | pu | pu | TAP (a) |%
 linedat = [1 4 0.080 0.370 0.00028 0
 2 3 0.723 1.050 0 0
 2 5 0.282 0.640 0 0
 3 4 0.0 0.266 0 0
 5 6 0.0 0.428 0 0
 6 4 0.97 0.0407 0.0003 0
 6 1 0.123 0.158 0.00028 0];