Calculate the effective k factor at a pipe junction where th

Calculate the effective \"k factor\" at a pipe junction where the flow and pressure demand are 450 gpm at 65 psi.

Solution

Solution:-

Given

Q = 450 gpm

P = 65 psi

k factor = Q/(P)1/2

k factor = 450/(65)1/2

k factor = 55.81 gpm/(psi)1/2       Answer