Approaches range from simplistic rules of thumb to scientific methods (e.g. NyquistShannon sampling theorem). On the easier end of the spectrum its commonplace to stipulate sample rates of 1 second or faster for Flow loops and 1-2 seconds for Pressure. Such loops react very quickly to changes in Controller Output. Not far behind are rates of 2-5 seconds for many Temperature and Level loops which characteristically possess slower dynamics.
When considering sample rate from a scientific or mathematical perspective, the guidelines are a bit more involved and beyond the scope of this blog post. Still, its generally accepted best-practice for the sample rate to be based on frequency or time based components of the process data. Basic formulas propose the use of data that is either 5-10 times faster than the Process Time Constant or 3-5 times faster than the Process Dead-Time.