A three-phase motor consumes 100kW @ 0.9 pf lagging. The motor has a line voltage of 480V. What is the corresponding line current magnitude? If the motor is delta connected, provide a phasor for the current in each line and each phase. Denote the voltage V_AB as having a zero degree angle and assume the voltages are a positive- sequence (abc) set.
Solution
P=1.732*V*I*COSQ=100*10^3
1.732*480*I*0.9=100*10^3
I=(100*10^3)/(1.732*480*0.9)=133.6 AMPERES.
IN DELTA CONNECTED LOAD
IL=1.732*IPH
VL=VPH
IA=133.6<0 AMPS
IB=133.6<-120 AMPS
IC=133.6<-240 AMPS
IAB=(133.6<0)/1.732=77.13<0 AMPSS
IBC=(133.6<-120)/1.732=77.13<-120 AMPS
ICA=(133.6<-240)/1.732=77.13<-240 AMPS