Consider the balanced threephase circuit operating at a freq

Consider the balanced three-phase circuit operating at a frequency of 60 Hz shown below. The circuit is connected to a generator with a line voltage of 36 kV - rms. The balanced three-phase load absorbed 6 MW of average power with a 0.707 lagging power factor. A bank f capacitors is connected in parallel with a balanced three-phase load to correct the power factor. Determine the value of the capacitor, C, that will raise the power factor to 0.92 lagging.