In electrical equipment rooms the illumination shall not be
     In electrical equipment rooms, the illumination shall not be controlled by automatic means only.  True  False NEC:  What is the ampacity of a 14 AWG, RHW conductor if it is run in a walk-in cooler that has an ambient temperature of 5 degree C?  15 amperes  18 amperes  24 amperes  30 amperes  NEC:  Cables and raceways parallel to framing members shall not be less than  from edge of framing member  1 1/4  1 1/2  1 3/4  1 1/8  NEC  A 120/240-volt, 3 wire service drop passing over a pedestrian sidewalk shall have a minimum clearance from final grade of how many ft?  10 ft (3.05m)  12 ft (3.66m)  15 ft (4.57m)  18 ft (5.49m)  NEC:  The minimum number of in. between the top surface of a finished grade and the top of a direct burial cable that is in a trench that is beneath a 3 in. (76.2mm) thick concrete slab is:  6 in. (152.4mm)  12 in. (305mm)  18 in. (457mm)  24 in. (610mm)  NEC:  Determine the minimum cubic in. required for three 12 AWG TW conductors passing through a box, five 14 AWG THHN conductors terminating in the box, two 10 AWG TW conductors terminating to a receptacle, and one 10 AWG equipment bonding jumper from the receptacle to the box.  12.00 in.^3 (196.8 cm^3)  14.25 in.^3 (233.7 cm^3)  16.75 in.^3 (274.7 cm^3)  29.25 in.^3 (315.7 cm^3)  NEC:   
  
  Solution
1) true
in electrical equipment rooms the illumination may be not be controlled by automatic means only.
according to NEC additional requirements of workspace a motion detector is acceptable if a manual override is provided