Conditions in one zone of a dualduct conditioning system are
Solution
Given inputs
TR = 75 F
RH=50 %
Thot =90 F
RHhot =20 %
Tcold = 52 F
RHcold =90 %
Ts = 14.2o C = 57.56 F
Patm = 101.325
Ws = 0.007
Sensible Heat factor = 0.65
Total zone load = 50 tons
Solution :
hR = enthalpy (airH2O, T = TR, R=RR,P = Patm)
Hhot = enthalpy (airH2O, T = Tcold,R= Rcold, P = Patm)
Hcold = enthalpy (airH2O, T = Tcold,R= Rcold, P = Patm)
hs = enthalpy (airH2O, T = Ts, w = ws, P = Patm)
vs = volume (airH2O, T = Ts, w = ws, P = Patm)
50*200/.9478 = ms*(hR-hs)
Hs = (mhot/ms)*hhot+(1-(mhot/ms))*hcold
Volsupply = ms*vs
HotColdRatio = mhot/(ms-mhot)
SOLUTION :
Hcold =29.57 C Hhot = 47.31 HotcoldRatio = 0.1573 hR = 47.83
Hs = 31.98 mhot = 90.49 ms = 665.9 Patm = 101.325
Rcold =0.9 Rhot = 0.2 RR = 0.5 Tcold = 11 C
Thot = 32 C TR = 24 C Ts = 14.2 VolSupply = 548.1
Vs =0.8232 ws = 0.007
Supply Volume = 548.1 m3 /min
Hot to Cold ratio = 0.1573
pyschometric chart http://www.uigi.com/UIGI_SI.PDF