721 On a hot September day a room has a sensi ble cooling lo
Solution
solution:
1)here initially supply air is supply at To=58 F or 14.44 c and Tw=17 C and room have condition to be maintained at Ti=76 F or 24.44 c with sensible heat load and latent heat load,as onlys upply air is present hence all air present in room is exhausted and hence to get air at 76 F we have to heat air in first case with heater,at that moment equation are as follows
BTu/hr=3798 kw
OASH=.0204*Q*(Ti-To)
OASH=20300 BTu/hr or 5.949 kw and latent OALH=9000 BTu/hr or 2.637 kw
as outside air has to take all load then supply air flow rate through heater is
OASH=.0204*Q*(Ti-To)
Q=29.16 m3/min or 1029.72 CFM
here from latent heat we can get supply air condition of humidity as follows
OALH=50*Q*(Wi-Wo)
Wi=.009 kg/kg of dry air
so we get Wo=.01080 kg/kg of dry air
from psychometrics table we gt that
Ho=enthalphy=42 kj/kg
relative humidity=100%
3)when external supply air is mixed with return air from room then we have
Qsupply=7.3623 m3/min
Qreturn=Qroom-Qsupply
Qroom=Qsupply=29.16 m3/min
we get
Qreturn=21.7971 m3/min
supply air To=94 F or 34.44 C
so mixed air dry bulb temperature is given by
Tmix=To*Qsupply+Ti*Qreturn/Qroom
Tmix=26.96 C
wet bulb temperature
Tow=76 F or 24.44 C
Tmix=To*Qsupply+Ti*Qreturn/Qroom
Tmix=18.87 C
from table we get enthalphy and moisture content as
ho=74 kj/kg
wo=.0146
hmix=50.07 kj/kg
wmix=.01041 kg/kg of dry air
total load=OASH+OALH+RSH+RLH
OASH=.0204*Qsupply*(To-Ti)=1.5019 kw
OALH=50*Q*(Wo-Wi)=2.0614 kw
total load=12.1493 kw
BTu/hr=3798 kw
refrigertion system capacity=12.1493/3.517=3.454 ton of refrigeration or TR 13118.292 BTU/ hr
if flow rate decresed by 50% the OASH and OALH is also decreases by 50%
OASH1=OASH/2=.75095 kw
OALH1=OALH/2=1.0307 kw
now total load=OASH1+OALH1+RSH+RLH=10.3676 kw
hence reduction is by 14.66% in refrigeration capacity but fresh air is also important ofr human comfort