The cooling tower CT capacity in tons of refrigeration TR an

The cooling tower (CT) capacity in tons of refrigeration (TR) and b. The effectiveness using the following data: - Water flow rate through CT: 120 m^3/h - Specific heat of water: 1 kCal/kg degree C - Inlet water temperature: 37 degree C - Outlet water temperature: 32degree C - Ambient wet bulb temperature (WBT): 29degree C

Solution

Considering that the tower doesnt follow evapouration:


a)Water flow rate = m = 120 m3/hr = 264 554.71 lb/hr

Specific heat of water =Cp =1 Kcal/Kg0C = 4.19 Kj/Kg0C

Change in Temperature = dT = 50C
Cooling tower capacity = mdT (Btu/hr)

= 1322773.55 Btu/hr

= 110.23 TonR

b) Effectiveness of cooling tower = = (ti - to) 100 / (ti - twb)

= (37-32)*100/(37-29)

=62.5%