To size the feeder please compute the receptacle load for a
Solution
ANSWER
1.for departmental stores the total number of receptacles given are 165. for each outlet the load is 180VA.
for 165 duplex receptacles the receptacle load is given as
Receptacle load = 165* 180VA = 29700VA
Answer
2. The maximum circuit power P= E* I = 120V * 15A = 1800VA
Then divide the power by the load per receptacle (180 volt-amperes) for no. of receptacles
No. of receptacles = Total power(P) / Load per receptacle
1800/180 = 10
A 120-volt, 15-amp circuit can supply 10 receptacles.